ΠΥΡΑΝΤΟΧΗ ΒΑΦΗ ΚΑΛΩΔΙΩΝ

BMA is an ablation coating mass for wiring and can be applied for either indoor and outdoor use.

Field of Application

  • Electrical cables of any material and thickness as well as cable trays made of steel or aluminium profiles
  • Permitted for indoor and outdoor use (refineries, industrial facilities etc.)

 

Certification

  • ETA-15/0237

 

Technical Data

Characteristics
Fire protection compound on the basis of water
Binding agent
Special dispersion – solvent-free
Pigments / fillers Non-combustible and flame-retardant pigments and fillers
pH-value Ca. 8
Viscosity
Thixotrop (160-220 dPas at 20 °C – 22 °C, Haake Viscotester VT-02)
Solids 66% – 76%
Dilution Clean water (max. 5 weight. – %)
Equipment cleaning
Clean with water immediately after use
Consumption
Approx. 2,05 kg/m2 for a dry film thickness of 1 mm
Surface
Surfaces must be stable, clean and free of grease and dust; steel and iron parts should be protected against corrosion in case of outdoor applications or in areas where condensed water may be developed.
Temperature resistance
The applied coating compound withstands temperatures from – 40 °C to + 80 °C, there is neither chemical break- down, discolouration nor a deterioration in its efficacy.